Skip to content

Copeland White-Rodgers 50M58-956 Integrated Furnace Control, York Direct OEM Replacement

Save 56%
Original price $482.69
Current price $211.18
SKU 50M58-956
Currently 5 in stock.

Copeland White-Rodgers 50M58-956 2-Stage Integrated Furnace Control for ECMx Blower Motors, York Direct OEM Replacement

Simple drop-in replacement for 120V York applications.

Direct drop-in replacement

  • Direct replacement for 120V original OEM control
  • Mounting matches original OEM model

Advanced diagnostics

  • Simple push-button fault recall
  • Tri-color LED displays status and fault codes for easy troubleshooting

Features:

  • Direct replacement for 120V original OEM control
  • Mounting matches original OEM model
  • Diagnostic LED indicators streamline installation and system troubleshooting
  • 120V air cleaner output and 120V humidifier output up to 1 Amp max
  • Factory standard safety timings and adjustable fan delay options
  • Replaceable automotive style fuse

Specifications:

Electrical Ratings (@ 77°F [25°C])

  • Input voltage:  120 VAC, 60 Hz (Class II transformer required)
  • Max. input current:  @ 24 VAC:  800mA + MV
  • Relay load ratings:  6.0 Amp @ 120V
  • 1st stage gas valve relay:  1.5amps @ 24 VAC, 60Hz
  • 2nd stage gas valve relay:  0.5 amps @ 24 VAC, 60Hz
  • Ignitor:  2.0 amps @ 132 VAC, 60Hz
  • Inducer relays:  2.2 FLA - 3.5 LRA @ 120 VAC
  • Humidifier load:  1.0 A max @ 120 VAC
  • Electronic air cleaner load:  1.0 A max @ 120 VAC
  • Circulator output:  12 mA RMS @ 30 VAC

Flame Current Requirements

  • Min. Current to ensure flame detection:  0.3 ua DC
  • Operating temp range:  -40° to 175°F (-40° to 80°C)
  • Humidity range:  5% to 93% relative hum. (non-condensing)
  • Flame response time:  2.0 sec (max)
  • Gases approved:  Natural, manufactured, mixed, liquid petroleum, and LP gas air mixtures
  • Board dimensions:  8.875” x 4.875”
  • Agency approvals:  UL

Timing Specifications (All times are in seconds, unless noted otherwise)

  • Pre-purge time:  15
  • Igniter warm-up time:  17
  • Trial for ignition period (TFI):  4
  • Ignition activation period (IAP):  3
  • Retries:  2 times
  • Valve sequence period:  12
  • Inter-purge:  30
  • Post-purge time:  15
  • Lock-out time:  300
  • Heat delay-to-fan-on:  30
  • Heat delay-to-fan-off*:  90/120/150/180
  • Cool delay-to-fan-on:  0
  • Cool delay-to-fan-off:  60
  • Automatic reset time:  60 mins

Kit Includes:

(1) 50M58-956 Integrated Furnace Control

(1) Installation Instructions

Spec Sheet

Instructions

Catalog Page

 

Cross References:

York:  031-03494-000, S1-03103494000, S1-33103494000

White-Rodgers:  50M58-242-01, 50M58-242-01B1