The ICM530 Series is 4 models of Type 1 and Type 2 three-phase surge Protective Devices for three-phase Delta and three-phase Wye configurations.
When a surge occurs, the ICM three-phase surge suppressor will absorb the surge up to the specified limitations of the device. ICM incorporates superior thermally protected metal oxide varistor technology into the three-phase surge suppressors, which allows for safe disabling of the surge elements when a surge exceeds the thermal limits of the device. There is a single status light on the controls which identifies operational status when illuminated.
The ICM 3-phase surge suppressors can be installed as a Type 1 or Type 2 device for both indoor and outdoor applications.
- Delta or Wye Configuration
- NEMA Type 4X watertight plastic enclosure for outdoor and indoor installation
- Green LED indicates surge protection present
- Easily connects to electrical panel or disconnect for indoor and outdoor applications
- UL Listed Type 1 or Type 2 SPD
SPECIFICATIONS:
-
Service voltage (3-Phase): 240 VAC Delta or 120/208 VAC Wye
-
Short Circuit Current Rating (SCCR): 200 kA
-
Nominal discharge current (In): 20kA
-
Maximum Surge Current: 150,000 amps
-
Protection mode:
- 3 for Delta configuration
- 6 for Wye configuration (neutral tied to ground)
-
Maximum Continuous Operation Voltage (MCOV):
- L-L: 300 VAC
- L-N: (for Wye configuration only): 150 VAC
-
VPR:
-
Delta L-L: 1200 VAC
-
Wye L-L: 1200 VAC
-
Wye L-N: 700 VAC
-
-
SPD type: Type 1 (can also be used in Type 2 applications)
-
Surge protection technology: TFMOV
-
Input power frequency: 50/60 Hz
REPLACES:
-
ABB: OVRHLDxx-120
-
ASCO: 420120Y, 420240D
-
Eaton: SP1-208Y, SP1-240D, SP2-208Y, SP2-240D
-
ERICO (Critec): TDX50C120/208, TDX50C120/240D
-
Intermatic: AG2083C3, L5F13Y1DG1
-
Leviton: 55208-ASA
-
Siemens: TPS3D, TPS3C
-
Square D: SDSA2040, SDSA2040D