Saniflo 044 Sanicondens Best Flat Condensate Pump & Neutralizer, 120V

The Sanicondens Best Flat is a low profile pump used to neutralize and pump condensate from condensing boilers, HVAC systems, water heater systems, etc. The Sanicondens Best Flat will pump condensate waste up to 15 feet in height and/or 150 feet away from a soil stack. 

  • Discharges the condensate waste through 3/8" vinyl tube. A non-return valve is included on the discharge connection provided with the system.
  • Comes with provisions for a ready-to-wire connection to an external overflow switch that will shut down the appliance or alert the consumer in the event of overflow. It also includes all necessary hardware for ease of installation; 20ft of vinyl tubing, inlet adapter, discharge adapter.
  • Discharges condensate from a condensing boiler or other condensate producing fixtures. The condensate will drain into the system via a side inlet or through a couple of inlets on top of the enclosure.
  • Comes equipped with a built-in neutralizer to raise pH levels for harsh HVAC applications. Neutralizing granules come included with the condensate pump. Will neutralize condensate from appliances up to 500,000 BTU/hour input.

2-in-1 low profile condensate pump which neutralizes and pumps away condensate.

  • Built-in neutralizer to raise pH levels for harsh HVAC applications
  • ↑ 15 Ft ↑ and/or ← 150 Ft →  
  • 500,000 BTU per hour
  • Equipped with all necessary hardware for easy installation

2 IN 1 CONDENSATE PUMP WITH BUILT-IN NEUTRALIZER FOR HARSH HVAC APPLICATIONS

Neutralizing agent (Part# 042) is used to raise the pH level from condensate being produced by condensing boilers, air conditioners, etc. The two quart capacity condensate pump comes equipped with all the necessary hardware for easy installation. It can be installed on top of flat surface or mounted on a wall. 

 

Product Sheet

 

Technical Specifications

Pump Type:
Condensate Pump
Electrical: 120V - 60Hz / 1.5 Amps (Max)
Motor: 1/30 HP oil-filled thermally protected motor
Operating Temperature: 160°F Max
Power Cord Length: 61-1/2 inches
Noise Level: ≤ 44 dBA (Lp) (measured at 3 ft.)
Discharge Pipe Diameter: 3/8"
Discharge Rate at 15 ft: 30 GPH
Discharge Rate at 3 ft: 86 GPH
Normal Running Time: 3-5 seconds (short bursts)
Capacity: 0.9 gallons / 3.4 liters
Inlets: 1" (top), 1" (side)
Method of Activation: Float / Microswitch
Weight: 12 lbs / 5.4 kg
Certifying Agencies: CSA (IPC, NSPC)
Recommended Accessories: Neutralizing granules (Part# 042)
Connections: Condensing boilers, HVAC systems, air conditioners