Bacharach 0024-8523 Fyrite® InTech® Combustion Analyzer with Protective Rubber Boot and Hard Carrying Case
Bacharach 0024-8523 Fyrite® InTech® Combustion Analyzer with Protective Rubber Boot and Hard Carrying Case
Handheld Combustion Analyzer for Residential Applications
Bacharach’s InTech® is the perfect tool for entry-level residential HVAC technicians providing readings for O2, CO, CO2, Combustion Efficiency and Temperature. The InTech® is available with pre-calibrated gas sensors to minimize downtime and maintenance costs. The Combustion mobile app (available for Android & iOS) allows users to create and send customizable combustion reports on-site.
The InTech® combustion analyzer is the perfect tool for entry-level and residential technicians who need to ensure safe operating conditions and determine combustion efficiency. The InTech® features 6 fuels in the North American configuration to suit a wide variety of applications.
The InTech® includes sensors for O2 and CO, with an option for an external NOx filter. The CO sensor can be replaced in the field without down time using pre-calibrated sensors. The InTech® calculates values like efficiency, CO2 and CO air-free to help monitor combustion processes effectively and accurately.
FEATURES
- All-in-one instrument makes combustion tuning fast and simple with readings for O2, CO, CO2, combustion efficiency, and temperature
- Combustion App allows users to quickly create custom reports with comments and send via email (available for Android & iOS)
- Automatic sensor protection helps technicians protect the analyzer in harsh environments, extending sensor life
- Ambient CO monitoring function allows technicians to check for dangerous CO levels
- Quick and easy sensor replacement in the field reduces downtime and doesn’t require calibration gas
All kits include:
- Probe with 12 in. sample tube (approximately 6 ft. total length), water trap and particulate filter
- 4x AA batteries
- User manual
- Hard carrying case
- Protective Rubber Boot
Product Data Sheet
Product Manual
Specifications:
Sensors: | Up to 2 |
Measuring Range: | 0 to 20.9% 0 to 2000 ppm |
Stack Temperature: | -4 to 1202 °F (-20 to 650 °C) |
User Interface: | Monochrome LCD w/Backlight |
Display Size: | 2.7 in. (69 mm) |
Power: | 4 × Alkaline Batteries |
Run Time: | 15 Hours (Alkaline Batteries) |
Warm-Up Time: | 30 to 60 seconds |
Digital Communications: | USB 2.0 (mini-B), IrDA |
Ambient Temperature: | 23 to 113 °F (-5 to 45 °C) |
Humidity: | 15 to 90% RH (non-condensing) |
Altitude: | 1 ATM ± 10% |
Product Dimensions (L×W×H): | 8" × 3.6" × 2.3" (20.3 × 9.1 × 5.8 cm) |
Product Weight: | 1 lb. (0.45 kg) including batteries |
Fuel Equations: | Natural gas, oil 2/6, kerosene, propane, butane, LPG, B5, KOKS, LEG, biofuel |
Approvals: | CE, EN 50379-1 , EN 50379-3 |
Internal Memory: | 10 Records |
Warranty: | 2 Years (including sensors) |
Printer: | IrDA + Bluetooth Printer (Optional) |
Country of Origin: | United States |