ICM Controls ICM530 3-Phase Surge Protective Device, Delta 240VAC or Wye 120/208VAC

The ICM530 Series is 4 models of Type 1 and Type 2 three-phase surge Protective Devices for three-phase Delta and three-phase Wye configurations. 

When a surge occurs, the ICM three-phase surge suppressor will absorb the surge up to the specified limitations of the device. ICM incorporates superior thermally protected metal oxide varistor technology into the three-phase surge suppressors, which allows for safe disabling of the surge elements when a surge exceeds the thermal limits of the device. There is a single status light on the controls which identifies operational status when illuminated. 

The ICM 3-phase surge suppressors can be installed as a Type 1 or Type 2 device for both indoor and outdoor applications. 

  • Delta or Wye Configuration 
  • NEMA Type 4X watertight plastic enclosure for outdoor and indoor installation 
  • Green LED indicates surge protection present 
  • Easily connects to electrical panel or disconnect for indoor and outdoor applications 
  • UL Listed Type 1 or Type 2 SPD 

  

SPECIFICATIONS:

  • Service voltage (3-Phase): 240 VAC Delta or 120/208 VAC Wye 

  • Short Circuit Current Rating (SCCR): 200 kA 

  • Nominal discharge current (In): 20kA 

  • Maximum Surge Current: 150,000 amps

  • Protection mode:

    • 3 for Delta configuration 
    • 6 for Wye configuration (neutral tied to ground) 
  • Maximum Continuous Operation Voltage (MCOV):

    • L-L: 300 VAC 
    • L-N: (for Wye configuration only): 150 VAC 

     

  • VPR:

    • Delta L-L: 1200 VAC

    • Wye L-L: 1200 VAC

    • Wye L-N: 700 VAC

     

  • SPD type: Type 1 (can also be used in Type 2 applications) 

  • Surge protection technology: TFMOV 

  • Input power frequency: 50/60 Hz 

 

REPLACES:

  • ABB: OVRHLDxx-120 

  • ASCO: 420120Y, 420240D 

  • Eaton: SP1-208Y, SP1-240D, SP2-208Y, SP2-240D 

  • ERICO (Critec): TDX50C120/208, TDX50C120/240D 

  • Intermatic: AG2083C3, L5F13Y1DG1 

  • Leviton: 55208-ASA 

  • Siemens: TPS3D, TPS3C 

  • Square D: SDSA2040, SDSA2040D