Skip to content
Edmondson Supply will be closed Tuesday, December 24th & Wednesday, December 25th to celebrate Christmas. Final guaranteed shipping time is 12pm EST Monday, December 23rd. Regular shipping will resume Thursday, December 26th.
Edmondson Supply will be closed Tuesday, December 24th & Wednesday, December 25th to celebrate Christmas. Final guaranteed shipping time is 12pm EST Monday, December 23rd. Regular shipping will resume Thursday, December 26th.

ICM Controls ICM292A Direct Spark Ignition Furnace Control Board - Replacement for Rheem 62-24140-04

Save 4%
Original price $160.95
Current price $155.23
SKU ICM292A
Currently 25 in stock.

ICM Controls ICM292A Direct Spark Ignition Furnace Control Board - Replacement for Rheem 62-24140-04

The ICM292A is a low-cost DSI gas ignition control that replaces the following Rheem model: 62-24140-04. The ICM292A has incorporated LED diagnostics to assist in troubleshooting.

Fault code information can be found in the application guide. Please refer application guide with the furnace installation manual for future reference.

.

  • Low cost form, fit and functional replacement for Rheem: 62-24140-04
  • Direct Spark Ignition (DSI) control
  • Microprocessor-based
  • Controls induced draft and indoor blower motor; humidifier output, spark ignitor and gas valve
  • Monitors timing, trial for ignition, flame sensing and lockout
  • 100% lockout safety feature
  • Compatible with LP or natural gas
  • Status LEDs for fault codes to aid in troubleshooting 

 

SPECIFICATIONS

  • Control Voltage:  24 VAC (18-30 VAC), 60Hz
  • Line Voltage:  115 VAC, 60Hz
  • Power cons: 0.3A plus gas valve current at 24 VAC
  • Operating temp: -40°F to 176°F (-40°C to 75°C)
  • Timing:
    • Pre-Purge:  30 seconds
    • Trial for Ignition:  7 seconds
    • Retries:  Two groups of two, 30 second delay within the group, and 3 minute delay between groups
    • Lockout:  1-hour
    • Post-Purge:  90, 120, 160 and 180 seconds
  • Inputs:
    • Power:  24 VAC and COM
    • Thermostat Interface:  R,W, Y, and G
    • System Switches:  Vent pressure and limit switches (main and over-temperature switches in series)
    • Flame Sensing
    • Heat Blower OFF Delay (miniature slide switch set)
  • Outputs:
    • Gas Valve: 3A Pilot Duty @ 120 VAC
    • Draft Inducer Motor: 3A max., 1/6 HP @ 125 VAC
    • Cool Blower: 16A max., 1/2 HP @ 277 VAC
    • Heat Blower: 14A max., 1/2 HP @ 277 VAC
    • Circulating Fan:12A max., 1 HP @ 125 VAC
    • Heat/Cool Fan: 10 A max., 1/2 HP @ 277 VAC
    • Electronic Air Cleaner: 10 A max., 1HP @ 125 VAC
    • Humidifier: 11 A max., 1/6 HP @ 125 VAC
  • LED Indicators:
    • Power, Green LED:  PWR
    • Status, Green LED:  OK
    • Flame Status, Yellow LED:  FLAME